In-rush current: FX-PPM/E: 100V AC Max. 50A < 5msec,
200V AC Max. 60A < 5msec FX-128M/E:100V AC Max. 50A < 7msec,
200V AC Max. 70A < 7mse FX2C-PPM: 100V AC Max. 40A < 5msec,
200V AC Max. 60A < 5msec
FX-16MT-ESS/UL Power consumption: FX-16M, 24MR-UA1 = 30VA
FX-24M = 35VA
FX-32M/E = 40VA
FX-48M/E, 64MR-UA1 = 50VA
FX-64M = 60VA
FX-80M = 70VA
FX-128M = 100VA
FX2C-64M, 96M = 80VA
FX2C-128M, 160M = 120VA
Class 3 ground
Earthing/Grounding FX-48MT-ESS/UL Mitsubishi plc
Use a cable at least 2mm2 (AWG14) to ground equipment. Ground
resistance must be less than 100W (class 3). Note that the ground
cable must not be connected to the
same ground as the power circuits. Grounding is recommended but
if a proper ground cannot be provided the PC will still operate
correctly without being grounded.
Signal Ground (SG); Each SG terminals should be linked with 2mm2
(AWG14) cable.The linked cable should then be grounded to earth
at only one point.
     If the system being installed uses the service supply from both
the PC and a powered extension block , then the 0V terminals
should be linked.
· DO NOT however, link the 24V terminals.
· NEVER connect an external power supply to the PC’s 24V terminal.
· External DC supplies should not compromise the SELV aspects of
the FX/FX2C products.

FX: Without extension block:FX-16M, FX-24M, FX-32M/E = 24V DC
Max. 250mA
Version changes:V 1.2
FX-48M/E, FX-64M, FX-80M, FX-128M = 24V DC, 400mA V 2.0
FX-48M/E, FX-64M, FX-80M, FX-128M = 24V DC, 460mA
MITSUBISHI MELSEC FX-48MT-ESS/UL Mitsubishi plc
120-240 VAC POWER SUPPLY, 2K MEMORY,TRANSISTOR OUTPUT,MITSUBISHI PLC
24 DIGITAL INPUT/24 DIGITAL OUTPUT
External supply FX-48MT-ESS/UL Mitsubishi plc
The example shown right, uses an external
power supply to activate the inputs

FX-48MT-ESS/UL Resistors and inputs connected in parallel;
Parallel resistance Rp: FX= 15kW, FX2C= 18kW. If resistance Rp
is less than the stated
value, then add Rb. See equation 1 for Rb calculation. Alternatively;
Current leakage:
FX=1.5mA;FX2C=1mA. If the current leakage is greater than the
stated value, then
add Rb.See equation 2 for Rb calculation
American Bureau of Shipping (ABS) Certificate number 94-KO43665-X
FX-16   128 MT-ESS / MR-ES
FX-8 í 48E (EX/EY/ER/E-R/E-S/E-T/E-ES/ESS)
FX2-40AW/AP FX-232AW FX-8AV
FX-2AD-PT FX-4AD FX-4AD-TC FX-2DA
FX-1HC FX-1PG
FX-48MT-ESS/UL PLC Mitsubishi PLC
GENERAL FEATURES
Input: 24 digital input S/S
Output: 24 transistor output
Power supply : 85 - 264V AC, 50/60 Hz
Internal relays: 1536 aux relay
Data register: 1000 MW
Timers: 256 timer relay
States: 1000 bit
FX-48MT-ESS/UL Counters: 256 standart
FX-48MT-ESS/UL High speed counters:
Max 6 32 bits up/down counting ,
Max frequency 20 Khz/ 2 khz
Operation processing time: Basic instruction :0,48 microsec.
-Applied instruction:10-100 microsec.
Max. allowable momentary power failure period:
Fuse (size) rateing:
(Æ 5 ´ 20 mm (0.2 ´ 0.79 inches))
FX-16M, 24M, 32M/E =3.15A,(type 50CT-032H)
FX-48M/E, 64M, 80M, 128M,FX2C-64M, 96M, 128M, 160M = 5A
(type 50CT-050H)
FX-48MT-ESS/UL Mitsubishi plc
FX Series Programmable Controllers Hardware Manual  (Pdf)
MELSEC MEDOC – Start-up guide FOR DOS (Pdf)
MX CHANGE FOR MELSEC MEDOC PLUS (Pdf)
Melsec Medoc plus Beginner´s Manual  (Pdf)
FX-48MT-ESS/UL Mitsubishi plc user manual / hand book